[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-935363":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},935363,605,1,"单选题","对厂房和仓库进行耐火等级检查时，符合规范要求的是（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","储存精密实验仪器的仓库，其耐火等级不应低于二级",true,{"key":16,"text":17,"correct":18},"B","粮食筒仓的耐火等级为三级",false,{"key":20,"text":21,"correct":18},"C","某燃煤锅炉房锅炉的总蒸发量为6 t／h，锅炉房耐火等级为三级",{"key":23,"text":24,"correct":18},"D","建筑面积为380m2的独立乙类单层厂房耐火等级为三级","厂房和仓库耐火等级的要求有以下几点：（1）使用或储存特殊贵重的机器、仪表、仪器等设备或物品时，建筑耐火等级不应低于二级。（2）高层厂房，甲、乙类厂房，使用或产生丙类液体的厂房和有火花、赤热表面、明火的丁类厂房，油浸变压器室、高压配电装置室、锅炉房、高架仓库、高层仓库、甲类仓库、多层乙类仓库和储存可燃液体的多层丙类仓库、粮食筒仓，其耐火等级不应低于二级。（3）单、多层丙类厂房，多层丁、戊类厂房，单层乙类仓库，单层丙类仓库，储存可燃固体的多层丙类仓库和多层丁、戊类仓库，粮食平房仓，其耐火等级不应低于三级。（4）建筑面积不大于300 m2的独立甲、乙类单层厂房，建筑面积不大于500 m2的单层丙类厂房或建筑面积不大于1000 m2的单层丁类厂房，燃煤锅炉房且锅炉的总蒸发量不大于4 t／h时，可采用三级耐火等级的建筑。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]