[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-935355":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},935355,605,2,"多选题","某新建的煤粉厂房，地上7层，层高3m，并采用自动灭火系统进行全保护。下列关于该厂房内建筑构件耐火极限的说法，正确的是（ ）。",[11,15,19,22,25],{"key":12,"text":13,"correct":14},"A","采用耐火极限为3．00h的防火墙",false,{"key":16,"text":17,"correct":18},"B","采用耐火极限为1．00h的屋顶承重构件",true,{"key":20,"text":21,"correct":18},"C","采用耐火极限为1．50h的楼板",{"key":23,"text":24,"correct":14},"D","采用耐火极限为2．50h的承重墙",{"key":26,"text":27,"correct":18},"E","采用耐火极限为1．50h的疏散楼梯","BCE","煤粉厂房的火灾危险性分类为乙类，由地上7层可判断耐火等级为一级，二级耐火等级的乙类厂房最多只允许6层，根据《建筑设计防火规范》GB 50016—2014（2018年版）3．2．9，甲、乙类厂房和甲、乙、丙类仓库内的防火墙，其耐火极限不应低于4．00h，A选项错误； 根据3．2．11，采用自动喷水灭火系统全保护的一级耐火等级单、多层厂房（仓库）的屋顶承重构件，其耐火极限不应低于1．00h，B选项正确； 根据表3．2．1，一级耐火等级建筑的楼板、承重墙和疏散楼梯的耐火极限分别不低于1．50h、3．0h、1．50h，D选项错误，CE选项正确。",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]