[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-935198":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},935198,605,2,"多选题","(2016年真题)某丙类厂房建筑高度为45m，对齐消防救援窗口进行防火检查。下列消防救援窗口设置的做法中，符合规范要求的是（??）。",[11,15,19,22,25],{"key":12,"text":13,"correct":14},"A","消防救援窗口采用易碎安全玻璃，并在外侧设置明显标志",true,{"key":16,"text":17,"correct":18},"B","每个防火分区设置1个消防救援窗口",false,{"key":20,"text":21,"correct":18},"C","消防救援窗口设置在3层以上楼层",{"key":23,"text":24,"correct":14},"D","消防救援窗口的净高和净宽均为1.20m",{"key":26,"text":27,"correct":14},"E","消防救援窗口的下沿距地面室内高度为1.2m","ADE","消防救援口是指设置在厂房、仓库、公共建筑的外墙上，便于消防员迅速进入建筑内部，有效开展人员救助和灭火行动的窗口。对消防救援口的检查从以下几方面进行： (1)消防救援口设置位置与消防车登高操作场地相对应。窗口的玻璃应易于破碎，并在外侧设置易识别的明显标志。 (2)消防救援口的净高度和净宽度均不小于1．00 m，窗口下沿距室内地面不宜大于1．20m。 (3)消防救援口沿建筑外墙在每层设置，设置间距不宜大于20 m，保证每个防火分区不少于2个。",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]