[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-935181":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},935181,605,2,"多选题","（2020年真题）某4层商场，每层划分为1个防火分区、3个防烟分区。对该商场消防设施下列检测结果中，符合现行国家标准要求的有（ ）。",[11,15,19,22,25],{"key":12,"text":13,"correct":14},"A","按下消防联动控制器上的三层某排烟口的开启按钮，相应的排烟口开",true,{"key":16,"text":17,"correct":18},"B","按下四层的一只手动火灾报警按钮，四层的加压送风口打开，加压送风",false,{"key":20,"text":21,"correct":18},"C","使三层同一防烟分区内的两只独立的感烟火灾探测器发出火灾报警，三层的所有排烟口打开，相应排烟风机启动",{"key":23,"text":24,"correct":18},"D","使四层同一防烟分区内的一只感烟火灾探测器和一只手动火灾报警器火灾报警信号，相应的防烟分区内的电动挡烟垂壁下降",{"key":26,"text":27,"correct":14},"E","关闭排烟风机进口总管上的280℃排烟防火阀，相应的排烟风机停止","AE","P427-446 参《火灾自动报警系统设计规范》（GB50115-2013）4.5.2排烟系统的联动控制方式应符合下列规定:1应由同一防烟分区内的两只独立的火灾探測器的报警信号，作为排烟口、排烟窗或排烟個开启的联动触发信号，并应由消防联动控制器联动控制排烟口、排烟窗或排烟阀的开启，同时停止该防烟分区的空气调节系統。2应由排烟口、排烟窗或排烟阀开启的动作信号，作为排烟风机启动的联动触发信号，并应由消防联动控制器联动控制排烟风机的启动",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]