[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-935176":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},935176,605,1,"单选题","(2016年真题) 对剩余电流式电气火灾监控系统进行检查时，应主要检查剩余电流式探测器安装情况。检查发现的下来做法中，正确的是（??）",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","将相线和PE线穿过剩余电流式探测器",false,{"key":16,"text":17,"correct":14},"B","将PE线和中性线穿过剩余电流式探测器",{"key":19,"text":20,"correct":21},"C","将相线和中性线穿过剩余电流式探测器",true,{"key":23,"text":24,"correct":14},"D","将相线、中性线和PE线穿过剩余电流式探测器","电气火灾监控探测器的安装要求：(1)根据设计文件的要求确定电气火灾监控探测器的安装位置，有防爆要求的场所，应按防爆要求施工。(2)剩余电流式探测器负载侧的N线(即穿过探测器的工作零线)不应与其他回路共用，且不能重复接地(即与PE线相连)；探测器周围应适当留出更换和标定的空间。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]