[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-935175":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},935175,605,1,"单选题","(2016年真题) 某建筑物内火灾自动报警系统施工结束后，调试人员对通过管路采样的吸气式火灾探测器进行调试。下列调试方式和结果中，不符合现行国家消防标准要求的是（??）",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","在其中一根采样管最末端（最不利处）采样孔加入试验烟，控制器在120s内发出火灾报警信号",false,{"key":16,"text":17,"correct":14},"B","断开其中一根探测器的采样管路，控制器在100s内发出故障信号",{"key":19,"text":20,"correct":21},"C","断开其中一根探测器的采样管路，控制器在120s内发出故障信号",true,{"key":23,"text":24,"correct":14},"D","在其中一根采样管最末端（最不利处）采样孔加入试验烟，控制器在100s内发出火灾报警信号","管路采样式吸气感烟火灾探测器的调试要求：逐一在采样管最末端(最不利处)采样孔加入试验烟，采用秒表测量探测器的报警响应时间，探测器或其控制装置应在120s内发出火灾报警信号。根据产品说明书，改变探测器的采样管路气流，使探测器处于故障状态，采用秒表测量探测器的报警响应时间，探测器或其控制装置应在100s内发出故障信号。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]