[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-935162":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},935162,605,1,"单选题","(2018年真题) 对某大型商业综合体的火灾自动报警系统的安装质量进行检查，下列检查结果中不符合现行国家标准《火灾自动报警系统施工验收规范》(GB 50166)的是（??）",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","在高度为 12m 的共享空间设置的红外光束感烟火灾探测器的光束轴线至顶棚的垂直距离为 1.5m",true,{"key":16,"text":17,"correct":18},"B","在商场顶棚安装的点型感烟探测器距多孔送风顶棚孔口的水平距离为 0.6m",false,{"key":20,"text":21,"correct":18},"C","在厨房内安装的可燃气体探测器位于天然管道及用气部位的上部顶棚处",{"key":23,"text":24,"correct":18},"D","在宽度为 24m 的餐饮区走道顶棚上安装的点型感烟探测器间距为 12.5m","红外光束感烟火灾探测器的光束轴线至顶棚的垂直距离宜为0.3～1.0m。P316-329",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]