[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-935161":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},935161,605,2,"多选题","(2017年真题) 根据现行国家标准《火灾自动报警系统施工及验收规范》(GB50166-2007)，下列火灾自动报警系统的功能中，应每季度进行检查和试验的有（??）",[11,15,18,21,25],{"key":12,"text":13,"correct":14},"A","分期分批试验探测器的动作及确认灯显示功能",true,{"key":16,"text":17,"correct":14},"B","试验火灾警报装置的声光显示功能",{"key":19,"text":20,"correct":14},"C","试验主、备电源自动切换功能",{"key":22,"text":23,"correct":24},"D","试验非消防电源强制切断功能",false,{"key":26,"text":27,"correct":14},"E","试验相关消防控制设备的控制显示功能","ABCE","根据《火灾自动报警系统施工及验收规范》(GB 50166—2007)规定，每季度应检查和试验火灾自动报警系统的下列功能，并按本规范附录F的要求填写相应的记录。①采用专用检测仪器分期分批试验探测器的动作及确认灯显示；②试验火灾警报装置的声光显示；③对主电源和备用电源进行1～3次自动切换试验；④用自动或手动检查消防控制设备的控制显示功能：",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]