[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-935158":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},935158,605,2,"多选题","（2019年真题）某消防技术服务机构对某会展中心的自动消防设施进行维护保养,下列做法和结果中,不符合现行国家标准要求的有（）。",[11,15,19,22,25],{"key":12,"text":13,"correct":14},"A","对1只感烟探测器喷烟直至报警,探测器所在区域显示器在5s后发出报警信号",true,{"key":16,"text":17,"correct":18},"B","断开消防控制室图形显示装置与其连接的各消防设备的连线,图形显示装置在1min时发出的故障信号",false,{"key":20,"text":21,"correct":14},"C","在同一防火分区内,1只手动报警按钮和1只感烟探测器同时发出火灾报警信号。该防火分区内用于防火分隔的防火卷帘直接下降至地面。",{"key":23,"text":24,"correct":14},"D","检查发现火灾显示盘损坏,维护人员直接将其拆下,并立即更换新的产品。",{"key":26,"text":27,"correct":18},"E","在消防控制室手动选择2个广播分区启动应急广播,该区域正在播音的背景音乐广播停止,消防应急广播启动","ACD","P329-335 区域显示器应在3s内正确接收和显示火灾报警控制器发出的火灾报警信号，故A选项说法错误 手动报警按钮报警信号不能用于联动控制防火卷帘的联动控制，故C选项说法错误 如探测器、模块或火灾显示盘等外控设备发生故障，可暂时将其屏蔽隔离，待修复后再取消屏蔽隔离，恢复系统正常，故D选项说法错误",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]