[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-935154":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},935154,605,1,"单选题","（2019年真题）某消防技术服务机构对某宾馆的火灾自动报警系统进行年度检测,下列检测结果中不符合现行国家标准《火灾自动报警系统施工及验收规范》国标50166要求的是（）",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","断开一个探测回路与控制器之间的连线56秒时控制器发出故障信号",false,{"key":16,"text":17,"correct":18},"B","报警控制器在故障状态下,使任一非故障部位的探测器发岀火灾报警信号,85秒时控制器发出火灾报警信号",true,{"key":20,"text":21,"correct":14},"C","将一个探测回路中任意探测器的接线断开,30秒时控制器发出故障信号",{"key":23,"text":24,"correct":14},"D","断开备用电源与控制器之间的连线，66秒时控制器发出故障信号","P316-329 在故障状态下，使任一非故障部位的探测器发出火灾报警信号，控制器应在1min内发出火灾报警信号，并应记录火灾报警时间。故B选项说法错误",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]