[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-935152":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},935152,605,1,"单选题","（2020年真题）某商业综合体设置了集中电源,集中控制型消防应急照明和疏散指示系统,根据现行国家标准《消防应急照明和疏散指示系统技术标准》（GB51309）,不属于该系统部件连接方式的是（ ）。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","应急照明控制器直接与应急照明集中电源连接",false,{"key":16,"text":17,"correct":14},"B","应急照明集中电源,直接与消防应急照明灯具连接",{"key":19,"text":20,"correct":14},"C","应急照明控制器直接与应急照明控制器连接",{"key":22,"text":23,"correct":24},"D","应急照明控制器直接与应急照明配电箱连接",true,"P380-382 集中电源集中控制型消防应急照明和疏散指示系统无应急照明配电箱",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]