[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-935150":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},935150,605,1,"单选题","(2016年真题)消防技术服务机构对某大型商场内设置的疏散照明设施进行检测。下列检测结果中不符合《建筑设计防火规范》（GB50016-2014）要求的是（??）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","避难间疏散照明的地面最低水平照度为10.0lx",false,{"key":16,"text":17,"correct":18},"B","营业厅疏散照明的地面最低水平照度为2.0lx",true,{"key":20,"text":21,"correct":14},"C","楼梯间疏散照明的地面最低水平照度为5.5lx",{"key":23,"text":24,"correct":14},"D","前室疏散照明的地面最低水平照度为6.0lx","建筑内消防应急照明灯具的照度应符合下列规定：疏散走道的地面最低水平照度不应低于1．0 lx。人员密集场所、避难层(间)内的地面最低水平照度不应低于3．0 lx；对于病房楼或手术部的避难间，不应低于10．0 lx。楼梯间、前室或合用前室、避难走道的地面最低水平照度不应低于5．0 lx。消防控制室、消防水泵房、自备发电机房、配电室、防烟与排烟机房，以及发生火灾时仍需正常工作的其他房间的消防应急照明，仍应保证正常照明的照度。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]