[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-935149":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},935149,605,1,"单选题","(2018年真题)消防技术服务机构对某高层写字楼的消防应急照明系统进行检测，下列检测结果中，不符合现行国家标准《建筑设计防火规范》(GB 50016)的是( )",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","在二十层楼梯间前室测得的地面照度值为 4.0lx",true,{"key":16,"text":17,"correct":18},"B","在二层疏散走道测得的地面照度值为 2.0lx",false,{"key":20,"text":21,"correct":18},"C","在消防水泵房切断正常照明前、后测得的地面照度值相同",{"key":23,"text":24,"correct":18},"D","在十六层避难层测得的地面照度值为 5.0lx","10.3.2 建筑内疏散照明的地面最低水平照度应符合下列规定： 1对于疏散走道，不应低于 1.0 lx； 2对于人员密集场所、避难层（间），不应低于 3.0 lx；对于老年人照料设施、病房楼或手术部的避难间，不应低于 10.0 lx； 3对于楼梯间、前室或合用前室、避难走道，不应低于 5.0 lx；对于人员密集场所、老年人照料设施、病房楼或手术部内的楼梯间、前室或合用前室、避难走道，不应低于 10.0lx。P309-313",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]