[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-935148":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},935148,605,1,"单选题","(2018年真题)对一家大型医院安装的消防应急照明和疏散指示系统的安装质量进行检查。下列检查结果中，符合现行国家标准《建筑设计防火规范》(GB50016)的是（ ）。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","消防控制室内的应急照明灯使用插头连接在侧墙上部的插座上",false,{"key":16,"text":17,"correct":14},"B","疏散走道的灯光疏散指示标志安装在距离地面1.1m的墙面上",{"key":19,"text":20,"correct":14},"C","主要疏散走道的灯光疏散指示标志的安装间距为30m",{"key":22,"text":23,"correct":24},"D","门诊大厅、疏散走道的应急照明灯嵌入式安装在吊顶上",true,"《建筑设计防火规范》(GB50016-2014)第10.3.4条,疏散照明灯具应设置在出口的顶部、墙面的上部或顶棚上;备用照明灯具应设置在墙面的上部或顶棚上。第10.3.5条,公共建筑、建筑高度大于54m的住宅建筑、高层厂房(库房)和甲、乙、丙类单、多层厂房,应设置灯光疏散指示标志,并应符合下列规定： ①应设置在安全出口和人员密集的场所的疏散门的正上方; ②应设置在疏散走道及其转角处距地面高度1.0m以下的墙面或地面上。灯光疏散指示标志的间距不应大于20m;对于袋形走道,不应大于10m;在走道转角区,不应大于1.0m。应急照明灯不应使用插头连接。P300-309",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]