[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-935147":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},935147,605,1,"单选题","(2016年真题) 对建筑进行防火检查时，应对建筑内设置的应急照明和疏散指示标志进行检查，下列关于公共建筑内安装应急照明灯具的说法中，错误的是()",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","在侧面墙上顶部安装时其底部距地面不得低于1.8m",true,{"key":16,"text":17,"correct":18},"B","消防应急照明灯具应均匀布置",false,{"key":20,"text":21,"correct":18},"C","在距地面1m以下墙面上置装时应采用嵌入式安装",{"key":23,"text":24,"correct":18},"D","在侧面墙上顶部安装时其底部距地面不得低于2m","消防应急照明灯具的安装：①消防应急照明灯具应均匀布置，最好安装在棚顶或距楼地面2m以上的侧面墙上(选项B符合要求)。②在侧面墙上顶部安装时，其底部距地面距离不得低于2m(选项A不符合要求，选项D符合)；在距地面1m以下侧面墙上安装时，应采用嵌人式安装(选项C符合要求)，其凸出墙面最大水平距离不应超过20mm，且应保证光线照射在安装灯具的水平线以下；不得安装在地面或距地面1～2m之间的侧面墙上。③吊装时，要采用金属吊杆或吊链，吊杆或吊链上端应固定在建筑结构件上。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]