[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-935140":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},935140,605,1,"单选题","（2020年真题）对某一类高层公共建筑的消防电源及其配电系统检查的下列结果中,不符合现行国家标准《建筑设计防火规范》（GB50016）的是（ ）",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","建筑总配电室内的消防电源配电柜分别有两个区域的35KV变电站供电",false,{"key":16,"text":17,"correct":14},"B","消防用电设备采用专业的供电回路,其配电箱独立设置",{"key":19,"text":20,"correct":21},"C","消防配电线路采用阻燃电缆,与其他配电线路分别布置在同一电缆井的两侧",true,{"key":23,"text":24,"correct":14},"D","消防控制室內设置的专用双电源配电箱设有自动切换装置","P367-370 消防配电线路宜与其他配电线路分开敷设在不同的电缆井、沟内；确有困难需敷设在同一电缆井、沟内时，应分别布置在电缆井、沟的两侧，且消防配电线路应采用矿物绝缘类不燃性电缆。C错误。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]