[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-935129":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},935129,605,1,"单选题","（2020年真题）某建筑地下车库设有防烟排烟系统，封装安装形式为明装，材料为钢板，钢板厚度设计未作要求。对风管进行进场检验,下列检验结果中不符合现行国家标准《建筑防烟排烟系统技术标准》（GB 51251）的是（ ）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","长边尺寸为450 mm的矩形排烟管道的板材厚度测量值为0.8 mm",false,{"key":16,"text":17,"correct":14},"B","长边尺寸为400 mm的矩形送风管道的板材厚度测量值为0.6 mm",{"key":19,"text":20,"correct":21},"C","长边尺寸为1100 mm的矩形排烟管道的板材厚度测量值为1.0 mm",true,{"key":23,"text":24,"correct":14},"D","长边尺寸为1000 mm的矩形，送风管道的板材厚度测量值为0.8mm","P353-355 《建筑防烟排烟系统技术标准》6.2.1风管应符合下列规定:长边尺寸为1100mm的矩形排烟管道的板材厚度应不小于1.2mm",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]