[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-935128":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},935128,605,1,"单选题","（2020年真题）某消防技术服务机枃对某建筑高度为58m的高层公共建筑的防烟楼梯间进行防火检査。下列检查结果中,不符合现行国家标准要求的是（ ）",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","楼梯间每个2层设置了1个常开式百叶送风口",false,{"key":16,"text":17,"correct":14},"B","前室每层设置了1个常闭式加压送风口,并设手动开启装置",{"key":19,"text":20,"correct":21},"C","楼梯间顶部设置了1个净面积为0.9㎡的固定窗",true,{"key":23,"text":24,"correct":14},"D","机械加压送风系统管道井的检修门为乙级防火门","P355-362 根据《建筑防烟排烟系统技术标准》（GB 51251）:3.3.11设置机械加压送风系统的封闭楼梯间、防烟楼梯间，尚应在其顶部设置不小于1m2的固定窗。靠外墙的防烟楼梯间，尚应在其外墙上每5层内设置总面积不小于2 m2的固定窗。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]