[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-935126":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},935126,605,1,"单选题","（2020年真题）某消防技术服务机构对某高层建筑的机械加压送风系统进行防火检查，根据现行国家标准《建筑防烟排烟系统技术标准》（GB 51251），下列防火检查结果中，不符合规范要求的是（ ）。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","风机房内的机械加压送风机为离心风机，其进风口直通室外",false,{"key":16,"text":17,"correct":14},"B","竖向安装在管道井内的机械加压送风管道为镀锌钢板风管",{"key":19,"text":20,"correct":14},"C","防烟楼梯间每隔3层安装一个常开式百叶送风口。",{"key":22,"text":23,"correct":24},"D","防烟楼梯间前室每层安装一个常开式加压送风口。",true,"P353-355 根据《建筑防烟排烟系统技术标准》（GB 51251）:3.3.6加压送风口的设置应符合下列规定:2前室应每层设一个常闭式加压送风口，并应设手动开启装置;",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]