[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-935125":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},935125,605,2,"多选题","（2020年真题）某消防技术服务机构对某建筑内设置的防烟排烟系统下列检查结果中，符合标准《建筑防烟排烟系统技术标准》（GB51251）的有（ ）。",[11,15,19,22,25],{"key":12,"text":13,"correct":14},"A","吊顶内的排烟管道采用玻璃棉隔热，与可燃物的最小距离为200mm",true,{"key":16,"text":17,"correct":18},"B","房间内排烟口距可燃物的最小距离为1.1m",false,{"key":20,"text":21,"correct":14},"C","风管穿越隔墙处，风管与隔墙之间的空隙采用水泥砂浆封堵",{"key":23,"text":24,"correct":14},"D","排烟风机直接安装在混凝土基础上，未设置减振装置",{"key":26,"text":27,"correct":18},"E","排烟风机安装在专用房间内，排烟风机外壳与墙壁之间的距离为0.5m","ACD","P355-362 排烟口距可燃物不小于1.5m;空间不小于600mm",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]