[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-935117":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},935117,605,1,"单选题","(2018年真题)对某大型超市设置的机械排烟系统进行验收，其中两个防烟分区的验收测试结果中，符合现行国家标准《建筑防烟排烟系统技术标准》（GB51251）的是（ ）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","开启防烟分区一的全部排烟口，排烟风机启动后测试排烟口处的风速为 13m／s",false,{"key":16,"text":17,"correct":14},"B","开启防烟分区一的全部排烟口，补风机启动后测试补风口处的风速为 9m／s",{"key":19,"text":20,"correct":21},"C","开启防烟分区二的全部排烟口，排烟风机启动后测试排烟口处的风速为 8m／s",true,{"key":23,"text":24,"correct":14},"D","开启防烟分区二的全部排烟口，补风机启动后测试补风口处的风速为 7m／s","送风口的风速不宜大于7m\u002Fs，排烟口的风速不宜大于10m\u002Fs。机械补风口的风速不宜大于10m\u002Fs，人员密集场所补风口的风速不宜大于5m\u002Fs；自然补风口的风速不宜大于3m\u002Fs。P278-284",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]