[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-935116":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},935116,605,1,"单选题","(2018年真题)对某大厦设置的机械防烟系统的正压送风机进行单机调试，下列调试方法和结果中，符合现行国家标准《建筑防烟排烟系统技术标准》(GB51251)的是()。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","模拟火灾报警后，相应防烟分区的正压送风口打开并联动正压送风机启动",false,{"key":16,"text":17,"correct":14},"B","经现场测定，正压送风机的风量值、风压值分别为风机铭牌的 97%、105%",{"key":19,"text":20,"correct":14},"C","在消防控制室远程手动启、停正压送风机，风机启动、停止功能正常",{"key":22,"text":23,"correct":24},"D","手动开启正压送风机，风机正常运转 1.0h 后，手动停止风机",true,"《建筑防烟排烟系统技术标准 GB51251-2017》7.2.5 送风机、排烟风机调试方法及要求应符合下列规定：手动开启风机，风机应正常运转2.0h，叶轮旋转方向应正确、运转平稳、无异常振动与声响。P278-284",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]