[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-935111":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},935111,605,2,"多选题","(2016年真题) 某12层公共建筑，防烟楼梯间及其合用前室采用正压送风系统，正压风机设置在屋顶，消防设施检测机构对该建筑物的正压送风系统进行检测，结果;十一层送风量满足设计值，五层正压送风量满足设计值，五层正压送风量为设计风值的80%，二层正风送风量为设计风值的60%，造成这一结果的可能原因是（??）",[11,15,19,22,25],{"key":12,"text":13,"correct":14},"A","风机风量压力不足",true,{"key":16,"text":17,"correct":18},"B","风道尺寸偏小",false,{"key":20,"text":21,"correct":18},"C","部件造型不当",{"key":23,"text":24,"correct":14},"D","风道泄露风口",{"key":26,"text":27,"correct":18},"E","位置不当","AD","从十一层至二层,送风量是越来越少的,如果风机送风量不大或不足,由于压力降的原因则只能满足离送风口近的楼层的风量要求,而满足不了离送风口远的楼层的风量要求,故选项A正确。此外,管道漏风的话也可能会出现送风量自上而下逐渐减少的情况,故选项D正确。",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]