[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-935109":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},935109,605,2,"多选题","（2019年真题）某20层大厦每层为一个防火分区，防烟楼梯间及前室安装了机械加压达风系统。下列对该系统进行联动调试的方法和测试结果中，符合现行国家标准《建筑防烟排烟系统技术标准》(GB51251)要求的有（）。",[11,15,18,21,25],{"key":12,"text":13,"correct":14},"A","手动开启第六层楼梯间前室内的常闭送风口，相应的加压送风机联动启动",true,{"key":16,"text":17,"correct":14},"B","使第九层的两只独立的感深测器报警，相应的送风口和加压送风机联动启动",{"key":19,"text":20,"correct":14},"C","风机联动启动后，在顶层楼梯间送风口处测得的风速为5m\u002Fs",{"key":22,"text":23,"correct":24},"D","按下第十层楼梯间前室门口的一只手动报警按钮，相应的加压送风机联动启动",false,{"key":26,"text":27,"correct":24},"E","风机联动启动后，测得第三层楼梯间前室上与走道之间的压差值为40Pa","ABC","P278-284 由加压送风口所在防火分区内的两只独立的火灾探测器或一只火灾探测器与一只手动火灾报警按钮的报警信号（“与”逻辑），作为送风口开启和加压送风机启动的联动触发信号，故D选项中说法错误 前室、合用前室、消防电梯前室、封闭避难层与走道之间的压差应为25~30Pa。故E选项说法错误",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]