[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-935106":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},935106,605,1,"单选题","（2019年真题）某消防救援机构对某商业综合体设置的挡烟垂壁进行监督检查，下列检查结果中，不符合现行国家标准《建筑防烟排烟系统技术标准》(GB51251)要求的是（）",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","活动挡烟垂壁的手动操作按钮安装在距楼地面1.4m的墙面上",false,{"key":16,"text":17,"correct":18},"B","活动挡烟垂壁与墙面、柱面的缝隙为70mm",true,{"key":20,"text":21,"correct":14},"C","由两块活动挡烟垂帘组成的连续性挡烟垂壁，挡烟垂帘搭接宽度为200mm",{"key":23,"text":24,"correct":14},"D","活动挡烟垂壁由无机纤维织物材料制作","P278-284 活动挡烟垂壁与建筑结构（柱或墙）面的缝隙不应大于60mm，由两块或两块以上的挡烟垂帘组成的连续性挡烟垂壁，各块之间不应有缝隙，搭接宽度不应小于100mm。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]