[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-935093":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},935093,605,2,"多选题","(2017年真题)根据现行国家标准《建筑灭火器配置验收及检查规范》(GB50444-2008)， 下列灭火器中， 应报废的有（??）。",[11,15,19,22,25],{"key":12,"text":13,"correct":14},"A","筒体表面有凹坑的灭火器",true,{"key":16,"text":17,"correct":18},"B","出厂期满2年首次维修后， 4年内又维修2次的干粉灭火器",false,{"key":20,"text":21,"correct":18},"C","出厂满10年的二氧化碳灭火器",{"key":23,"text":24,"correct":14},"D","无间隙喷射机构的手提式灭火器",{"key":26,"text":27,"correct":14},"E","筒体为平底的灭火器","ADE","根据《建筑灭火器配置验收及检查规范》(GB 50444—2008)规定，灭火器的维修期限应符合表2．3．3中的规定。二氧化碳和干粉灭火器的维修期限：出厂期满5年；首次维修以后每满2年，选项B错误。筒体严重锈蚀，锈蚀面积大于、等于筒体总面积的1／3，表面有凹坑，选项A正确。筒体为平底等结构不合理，选项E正确。没有间歇喷射机构的手提式，选项D正确。灭火器出厂时间达到或超过表2．3-4规定的报废期限时应报废。干粉灭火器报废期限是10年，二氧化碳灭火器报废期限是12年，选项C错误。",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]