[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-935082":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},935082,605,1,"单选题","（2020年真题）某消防技术服务机构对某单位安装的干粉灭火系统进行了检查。下列检查结果不符合现行国家标准《干粉灭火系统设计规范》（GB50347）要求的是（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","A预制干粉灭火装置灭火剂的冲装量为120kg",false,{"key":16,"text":17,"correct":18},"B","预制干粉灭火装置的管道长度为25m",true,{"key":20,"text":21,"correct":14},"C","预制干粉灭火装置的工作压力为2.5MPa",{"key":23,"text":24,"correct":14},"D","—个防护区内设置了两套预制干粉灭火装置，两套装置同时启动","P315-324 根据《干粉灭火系统设计规范》（GB50347）:3.4.1予制灭火装置应符合下列规定:1灭火剂储存量不得大于150kg。2管道长度不得大于20m。3工作压力不得大于2.5 MPa。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]