[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-935077":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},935077,605,1,"单选题","(2018年真题) 消防技术服务机构对某单位设置的预制干粉灭火装置进行验收前检测。根据现行国家标准《干粉灭火系统设计规范》(GB50374)，下列检测结果中，不符合规范要求的是( )",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","1个防护区内设置了5套预制干粉灭火装置",true,{"key":16,"text":17,"correct":18},"B","干粉储存容器的存储压力为2.5MPa",false,{"key":20,"text":21,"correct":18},"C","预制干粉灭火装置的灭火剂储存量为120kg",{"key":23,"text":24,"correct":18},"D","预制干粉灭火装置的管道长度为15m","预制灭火装置应符合下列规定: 1 )灭火剂储存量不得大于150kg。 2) 管道长度不得大于20m 。 3 )工作压力不得大于2.5 MPa。 (2 )一个防护区或保护对象宜用一套预制灭火装置保护。 (3)一个防护区或保护对象所用预制灭火装置最多不得超过4 套，并应同时启动，其动作响应时间差不得大于2s 。P247-254",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]