[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-935068":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},935068,605,1,"单选题","(2018年真题)消防技术服务机构对某石化企业安装的低倍数泡沫灭火系统进行日常检查与维护。维保人员开展的下列检查与维护工作中，不符合现行国家标准《泡沬灭火系统施工及验收规范》(GB50281)的是( )",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","每周以手动或自动控制方式对消防泵和备用泵进行一次启动试验",false,{"key":16,"text":17,"correct":14},"B","每月对低倍数泡沫产生器、泡沫比例混合装置、泡沫喷头等外观是否完好无损进行检查",{"key":19,"text":20,"correct":21},"C","每年对除储罐上泡沫混合液立管外的全部管道进行冲洗，清除锈渣",true,{"key":23,"text":24,"correct":14},"D","每两年对系统进行喷泡沫试验","每半年除储罐上泡沫混合液立管和液下喷射防火堤内泡沫管道及高倍数泡沫产生器进口端控制阀后的管道外，其余管道应全部冲洗，清除锈渣。P239-242",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]