[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-935066":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},935066,605,1,"单选题","(2017年真题)对某建筑的高倍数泡沫灭火系统进行检查后得出下列结论，其中不符合现行国家消防技术标准要求的是（??）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","高倍数泡沫产生器的高度应在泡沫淹没深度以上",false,{"key":16,"text":17,"correct":18},"B","高倍数泡沫产生器的出口设置导泡筒时，导泡筒的横截面面积为泡沫产生器出口横截面面积的1.2倍",true,{"key":20,"text":21,"correct":14},"C","固定安装的高倍数泡沫产生器前设置了管道过滤器、压力表和手动阀门",{"key":23,"text":24,"correct":14},"D","高倍数泡沫灭火系统干式水平管道最低点设置了排液阀，且坡向排液阀的管道坡度为3%","高倍数泡沫产生器的出口设置导泡筒时，导泡筒的横截面面积为泡沫产生器出口横截面面积的1.05~1.10倍",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]