[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-935057":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},935057,605,1,"单选题","（2020年真题）下列对高压二氧化碳灭火系统管道气密性试验的方法和结果判定中，不符合现行国家标准《气体灭火系统施工及验收规范》（GB 50263）的是（ ）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","进行气密性试验时，压力升至规范要求的试验压力值用时119s",false,{"key":16,"text":17,"correct":14},"B","达到规范要求的试验压力后，关断试验气源，3min内压力下降不超过试验压力的10%",{"key":19,"text":20,"correct":21},"C","灭火剂输送管道的气密性试验介质为空气，试验压力为8.8MPa",true,{"key":23,"text":24,"correct":14},"D","气动管道的气密性试验压力为驱动气体储存压力的1倍","P270-275 15×2\u002F3=10对高压二氧化碳灭火系统，水压试验：应取15.0 MPa，气密性试验压力应按下列规定取值：对灭火剂输送管道，应取水压强度试验压力的2\u002F3。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]