[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-935054":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},935054,605,2,"多选题","（2020年真题）某高层建筑内的高低压配电室采用七氟丙烷气体灭火系统进行防护，最大防护区灭火剂设计用量为705kg，储瓶间内设置6个150L灭火剂瓶，灭火剂充装密度为800kg\u002Fm3。根据现行国家标准《气体灭火系统施工及验收规范》（GB50263，对该气体灭火系统进行系统功能验收时，应做的试验项目有（ ）",[11,15,18,21,25],{"key":12,"text":13,"correct":14},"A","模拟启动实验",true,{"key":16,"text":17,"correct":14},"B","模拟喷气实验",{"key":19,"text":20,"correct":14},"C","主用备用电源切换试验",{"key":22,"text":23,"correct":24},"D","主用备用灭火器触屏模拟切换操作试验",false,{"key":26,"text":27,"correct":24},"E","手动应急启动装置动作试验","ABC","P270-275 参《气体灭火系統施工及验收规范》（GB50263）：7.4.1系统功能验收时，应进行模拟启动试验，并合格。7.4.2系统功能验收时，应进行模拟喷气试验，并合格。7.4.3系统功能验收时，应对设有灭火剂备用量的系统进行模拟切换操作试验，并合格7.4.4系统功能验收时，应对主用、备用电源进行切换试验，并合格。",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]