[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-935037":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},935037,605,2,"多选题","(2017年真题) 某单位的图书馆书库采用无管网七氟丙炕气体灭火装置进行防护， 委托消防检查机构对该气体灭火系统进行检测。 下列检测结果中， 符合现行国家消防技术标准要求的有（??）。",[11,15,18,22,25],{"key":12,"text":13,"correct":14},"A","系统仅设置自动控制、 手动控制两种启动方式",true,{"key":16,"text":17,"correct":14},"B","防护区内设置10台预制灭火装置",{"key":19,"text":20,"correct":21},"C","防护区门口未设手动与自动控制的转换装置",false,{"key":23,"text":24,"correct":21},"D","储存容器的充装压力为4.2MPa",{"key":26,"text":27,"correct":21},"E","气体灭火系统采用自动控制方式","AB","对气体灭火系统预制灭火装置的检查要求有： (1)一个防护区设置的预制灭火系统，其装置数量不宜超过10台。 (2)同一防护区设置多台装置时，其相互间的距离不得大于10 m。 (3)防护区内设置的预制灭火系统的充压压力不应大于2．5 MPa。 (4)预制灭火系统应设自动控制和手动控制两种启动方式。",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]