[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-935035":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},935035,605,2,"多选题","（2019年真题）某地下档案库房，设置了全淹没二氧化碳灭火系统，对该气体灭火系统的防护区进行防火检查，下列检查结果中，不符合现行国家标准要求的有（）",[11,15,19,22,25],{"key":12,"text":13,"correct":14},"A","防护区入口附近未设置气体灭火控制盘",false,{"key":16,"text":17,"correct":18},"B","防护区的入口处明显位置未配置专用的空气呼吸器或氧气呼吸器",true,{"key":20,"text":21,"correct":18},"C","防护区内未设置机械排风装置",{"key":23,"text":24,"correct":14},"D","系统管道未设置防静电接地",{"key":26,"text":27,"correct":18},"E","防护区出入口未设手动、自动转换装置","BCE","P211-215 设有气体灭火系统的场所，宜配置空气呼吸器。故B选项说法不正确 灭火后的防护区应通风换气，地下防护区和无窗或设固定窗扇的地上防护区，应设置机械排风装置，排风口宜设在防护区的下部并应直通室外，故C选项说法不正确 采用二氧化碳灭火系统的防护区必须在防护区出入口设手动、自动转换装置，故E选项说法不正确",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]