[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-935034":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},935034,605,1,"单选题","（2019年真题）根据现行国家规定《气体灭火系统施工及验收规范》(GB50263)，关于低压二氧化碳灭火系统管道强度试验及气密性试验的说法，正确的是（）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","管道气压强度试验压力应为设计压力的1.5倍",false,{"key":16,"text":17,"correct":14},"B","气密性试验前应进行吹扫，吹扫时管道末端的气体流速不应小于10m\u002Fs",{"key":19,"text":20,"correct":21},"C","经气压强度试验合格且在试验后未拆卸过的管道可不进行气密性试验",true,{"key":23,"text":24,"correct":14},"D","采用气压强度试验代替水压强度试验时，试验压力应为60%水压强度试验","P215-217 当水压强度试验条件不具备时，可采用气压强度试验代替。气压强度试验压力取值：二氧化碳灭火系统取80 %水压强度试验压力，IG 541混合气体灭火系统取10.5 MPa，卤代烷1301灭火系统和七氟丙烷灭火系统取1.15倍最大工作压力。故D选项说法错误 低压二氧化碳系统水压试验压力为4.0 MPa，故其气压试验压力应为4*80%=3.2MPa，故A选项说法错误 灭火剂输送管道在水压强度试验合格后，或气密性试验前，应进行吹扫。吹扫管道可采用压缩空气或氮气，吹扫时，管道末端的气体流速不应小于20 m\u002Fs，采用白布检查，直至无铁锈、尘土、水渍及其他异物出现。故B选项错误",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]