[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-935031":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},935031,605,1,"单选题","（2020年真题）某消防技术服务机构对某机房内设置的1套全淹没开式细水雾灭火系统进行了防火检查。下列检查结果中，不符合现行国家标准《细水雾灭火系统技术规范》（GB 50898）的是（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","分区控制阀为常闭信号阀，安装在防护区内",true,{"key":16,"text":17,"correct":18},"B","该系统保护的防护区数量为2个",false,{"key":20,"text":21,"correct":18},"C","系统管道之间采用氩弧焊工艺对口焊接",{"key":23,"text":24,"correct":18},"D","泵组吸水管上的变径处采用偏心大小头","P238-248 根据《细水雾灭火系统技术规范》3.3.2开式系统应按防护区设置分区控制阀。每个分区控制阀上或阀后邻近位置，宜设置泄放试验阀。3.3.4分区控制阀宜靠近防护区设置，并应设置在防护区外便于操作、检查和维护的位置。故选项A不符合。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]