[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-935027":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},935027,605,1,"单选题","(2017年真题) 某消防工程施工单位的人员在细水雾灭火系统调试过程中，对系统的泵组进行调试。根据现行国家标准《细水雾灭火系统技术规范》GB50898，下列泵组调试结果中，不符合要求的是()。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","以自动方式启动泵组时，泵组立即投入运行",false,{"key":16,"text":17,"correct":18},"B","以备用电源切换方式切换启动泵组时，泵组10s投入运行",true,{"key":20,"text":21,"correct":14},"C","采用柴油泵作为备用泵时，柴油泵的启动时间为5s",{"key":23,"text":24,"correct":14},"D","控制柜进行空载和加载控制调试时，控制柜正常动作和显示","《细水雾灭火系统技术规范》GB 50898-2013,4.4.3 泵组调试应符合下列规定： 1.以自动或手动方式启动泵组时，泵组应立即投入运行。选项A正确; 2.以备用电源切换方式或备用泵切换启动泵组时，泵组应立即投入运行。选项B错误; 3.采用柴油泵作为备用泵时，柴油泵的启动时间不应大于5s。选项C正确; 4.控制柜应进行空载和加载控制调试，控制柜应能按其设计功能正常动作和显示。选项D正确。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]