[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-935025":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},935025,605,1,"单选题","（2020年真题）某企业柴油发电机房设有水喷雾灭火系统，根据现行国家标准《水喷雾灭火系统技术规范》（GB 50219），对该水喷露灭火系统的雨淋报警阀组进行调试时，不需要使用到的检测工具是（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","微压计",true,{"key":16,"text":17,"correct":18},"B","流量计",false,{"key":20,"text":21,"correct":18},"C","秒表",{"key":23,"text":24,"correct":18},"D","声强计","P227-231 参《水喷雾灭火系统技术规范》8.4.8雨淋报警阀调试宜利用检测、试验管道进行。自动和手动方式启动的雨淋报警阀应在15s之内启动;公称直径大于200mm的雨淋报警阀调试时，应在60s之内启动，雨淋报警阀调试时，当报警水压为0.05MPa时，水力警铃应发出报警铃声。检查数量:全数检查。检查方法:使用压力表、流量计、秒表、声强计测量检查，直观检查。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]