[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-935021":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},935021,605,1,"单选题","(2018年真题)酒店设置有水喷雾灭火系统，检查中发现雨淋报警阀组自动滴水阀漏水。下列原因分析中，与该漏水现象无关的是()",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","系统侧管道中余水未排净",false,{"key":16,"text":17,"correct":14},"B","雨淋报警阀密封橡胶件老化",{"key":19,"text":20,"correct":21},"C","雨淋报警阀组快速复位阀关闭",true,{"key":23,"text":24,"correct":14},"D","雨淋报警阀阀瓣密封处有杂物","雨淋报警阀组常见故障分析、处理 1.自动滴水阀漏水 故障原因分析。 1）产品存在质量问题。 2）安装调试或者平时定期试验、实施灭火后，没有将系统侧管内的余水排尽。 3）雨淋报警阀隔膜球面中线密封处因施工遗留的杂物、不干净消防用水中的杂质等导致球状密封面不能完全密封。P180-181",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]