[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-935019":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},935019,605,1,"单选题","(2018年真题) 根据现行国家标准《水喷雾灭火系统技术规范》(GB50219)，关于水喷雾灭火系统管道水压试验的说法，正确的是( )。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","水压试验时应采取防冻措施的最高环境温度为4℃",false,{"key":16,"text":17,"correct":18},"B","不能参与试压的设备，应加以隔离或拆除",true,{"key":20,"text":21,"correct":14},"C","试验的测试点宜设在系统管网的最高点",{"key":23,"text":24,"correct":14},"D","水压试验的试验压力应为设计压力的1.2倍","A选项，水压试验时环境温度不宜低于5度，当低于5度 时，水压试验应采取防冻措施。 C选项, 水压强度试验的测试点应设在系统管网的最低点. D选项, 在管材类型为钢管的压力管道的水压强度试验中，当系统设计工作压力小于或等于1.0 MPa 时，水压强度试验压力应为设计工作压力的1.5 倍，并不应低于1.4 MPa,当系统设计工作压力大于1.0 MPa 时，水压强度试验压力应为该工作压力加0.4 MPa 。P177-180",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]