[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-935018":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},935018,605,1,"单选题","（2019年真题）某髙层建筑内的柴油发电机房设置了水喷雾灭火系统,水雾喷火的有效喷射程为2.5m,雾化角为90°,喷头与被保护对象的距离为1.0m,某消防技术服务机构对该系统进行检测,根据现行国家标的准《水喷雾灭火系统技术规范》(GB50219),下列检测结果中,符合规范要求的是（）",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","水雾喷头的平面布置方式为矩形,喷头间距为1.5m",false,{"key":16,"text":17,"correct":14},"B","顶部喷头的安装坐标偏差值为50mm",{"key":19,"text":20,"correct":14},"C","侧向喷头与被保护对象的安装距离偏差值为100m",{"key":22,"text":23,"correct":24},"D","管道支架与水雾喷头之间的距离为0.4m",true,"P177-180 根据《水喷雾灭火系统技术规范》中8.3.14条规定，管道支、吊架与水雾喷头之间的距离不应小于0.3m，与末端水雾喷头之间的距离不宜大于0.5m。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]