[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-935015":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},935015,605,1,"单选题","（2020年真题）某地下停车场无吊顶。设有预作用自动喷水灭火系统，某消防技术服务机构，对该系统中的喷头安装质量进行检查，下列检查结果中不符合现行国家标准《自动喷水灭火系统施工及验收规范》的是（ ）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","直立型标准覆盖面，洒水喷头溅水盘与顶板的距离为100mm",false,{"key":16,"text":17,"correct":14},"B","同—配水支管上安装的洒水喷头的间距为3.0m",{"key":19,"text":20,"correct":21},"C","通风管道覆面下安装的喷头类型为下垂型标准覆盖面洒水喷头",true,{"key":23,"text":24,"correct":14},"D","喷水距梁的水平距离为1.2米，喷头溅水盘距梁底的垂直距离为250mm","P195-210 C:预作用系统，采用直立型或干式下垂型。喷规表7.2.1表格",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]