[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-935014":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},935014,605,1,"单选题","（2020年真题）对某办公楼的自动喷水灭火系统的水流指示器进行功能检查时，在第五层末端试水装置处以1.5L\u002Fs的流量放水，消防控制室未收到该层水流指示器的动作反馈信号。下列关于未收到动作反馈信号的原因分析中，可以排除的是（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","水流指示器前的信号蝶阀未完全打开",true,{"key":16,"text":17,"correct":18},"B","与水流指示器链接的监视模块故障",false,{"key":20,"text":21,"correct":18},"C","水流指示器的信号反馈线路接线不实",{"key":23,"text":24,"correct":18},"D","水流指示器的叶片被异物、杂质等卡阻","P195-210 放水流量≥37.5 L\u002Fmin时，水流指示器必须报警。在第五层末端试水装置处以1.5L\u002Fs的流量放水，水流指示器应动作。根据选项可排出A",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]