[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-935011":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},935011,605,1,"单选题","（2020年真题）某单位对进场的湿式报瞽阀组进行渗漏检验，下列试验方法及结果中符合现行国家标准《自动喷水灭火系统施工及验收规范》（GB 50261）的是（ ）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","试验压力为报警阀额定工作压力的1.0倍，保压20min，阀瓣处无渗漏",false,{"key":16,"text":17,"correct":14},"B","试验压力为报警阀额定工作压力的1.2倍，保压15min，阀瓣处无渗漏",{"key":19,"text":20,"correct":21},"C","试验压力为报警阀额定工作压力的2.0倍，保压5min，阀瓣处无渗漏",true,{"key":23,"text":24,"correct":14},"D","试验压力为报警阀额定工作压力的1.5倍，保压10min，阀瓣处无渗漏","P191-195 根据《自动喷水灭火系统施工及验收规范》GB 50261-2017 3.2.8-6,报警阀应进行渗漏试验。试验压力应为额定工作压力的2倍，保压时间不应小于5min。C正确。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]