[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-935009":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},935009,605,2,"多选题","（2020年真题）某医院综合楼地上各层设置湿式自动喷水灭火系统，地下1层设置预作用自动喷水灭火系统。对该自动喷水灭火系统检测的下列结果中，符合现行国家标准《自动喷水灭火系统施工及验收规范》的有（ ）。",[11,15,19,22,25],{"key":12,"text":13,"correct":14},"A","打开第2层的末端试水装置，在距离水力警铃0.3米远处测得的声强为65dB",false,{"key":16,"text":17,"correct":18},"B","打开第4层的末端试水装置后，120秒消防水泵自动启动",true,{"key":20,"text":21,"correct":14},"C","使地下1层的一只感烟火灾探测器，发出报警信号预作用报警阀组启动",{"key":23,"text":24,"correct":18},"D","手动开启预作用阀组后90s，预作用系统处于开启状态的末端试水装置出水",{"key":26,"text":27,"correct":18},"E","打开消防水泵出水管上的试水阀，手动启泵后切换备用电源，消防水泵在50s时开启","BDE","P195-210 A选项错误∶应该是3m处，不小于70dB；C选项错误，不满足2路感烟\u002F一路感烟+手报的联动开阀信号；D选项正确，根据场所，设置的应该是单连锁，管道充水时间≤2min。",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]