[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-935004":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},935004,605,1,"单选题","(2015年真题) 闭式自动喷水灭火系统施工安装前，需对已进场的闭式喷头进行密封性能试验。下列情况中，符合相关施工验收规范要求的是（）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","施工单位按规范要求抽样并使用专用试验装置进行密封性能试验",true,{"key":16,"text":17,"correct":18},"B","密封性能试验压力为3MPa，保压时间1min",false,{"key":20,"text":21,"correct":18},"C","施工单位按每批喷头总数量的1%抽样送国家法定检测机构进行密封性能试验",{"key":23,"text":24,"correct":18},"D","施工单位按每批喷头5只喷头抽样送国家法定检测机构进行密封性能试验","自动喷水灭火系统中闭式喷头密封性能试验检查要求有： (1)密封性能试验的试验压力为3．0 MPa，保压时间不少于3 min。 (2)随机从每批到场喷头中抽取1％，且不少于5只作为试验喷头。当1只喷头试验不合格时，再抽取2％，且不少于10只的到场喷头进行重复试验。 (3)试验以喷头无渗漏、无损伤判定为合格。累计2只以及2只以上喷头试验不合格的，不得使用该批喷头。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]