[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-935001":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},935001,605,1,"单选题","(2016年真题)检查自动喷水灭火系统，湿式报警阀前压力为0.35Mpa，打开湿式报警阀组试水阀，以1.2L\u002FS的流量防火，不带延迟器的水力警铃最迟在（??）S内发出报警铃声。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","5",false,{"key":16,"text":17,"correct":14},"B","30",{"key":19,"text":20,"correct":21},"C","15",true,{"key":23,"text":24,"correct":14},"D","90","《自动喷水灭火系统施工及验收规范》(GB50261—2017)第7．2．5．1条规定，湿式报警阀调试时，在末端装置处放水，当湿式报警阀进口水压大于0．14MPa、放水流量大于1L／s时，报警阀应及时启动；带延迟器的水力警铃应在5～90s内发出报警铃声，不带延迟器的水力警铃应在15s内发出报警铃声；压力开关应及时动作，启动消防泵并反馈信号。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]