[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-934998":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},934998,605,1,"单选题","(2017年真题) 某消防工程施工单位在调试自动喷水灭火系统时，使用压力表、流量计、秒表、声强计和观察检查的方法对雨淋阀组进行调试，根据现行国家标准《自动喷水灭火系统施工及验收规范》GB50261，关于雨淋阀调试的说法中，正确的是()。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","自动和手动方式启动公称直径为80mm的雨淋阀，应在15s内启动",true,{"key":16,"text":17,"correct":18},"B","公称直径大于200mm的雨淋阀调试时，应在80s内启动",false,{"key":20,"text":21,"correct":18},"C","公称直径大于100mm的雨淋阀调试时，应在30s内启动",{"key":23,"text":24,"correct":18},"D","当报警水压为0.15MPa时，雨淋阀的水力警铃应发出报警铃声","",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]