[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-934992":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},934992,605,1,"单选题","(2018年真题)根据现行国家标准《自动喷水灭火系统施工及验收规范》(GB50261)对自动喷水灭火系统报警阀进行调试，下列调试结果中，不符合现行国家标准要求的是( )。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","湿式报警阀进水口水压为0.15MPa、放水流量为1.1L\u002FS时，报警阀组及时启动",false,{"key":16,"text":17,"correct":18},"B","雨淋报警阀动作后压力开关在25s时发出动作信号",true,{"key":20,"text":21,"correct":14},"C","湿式报警阀启动后，不带延迟器的水力警铃在14s时发岀报警铃声",{"key":23,"text":24,"correct":14},"D","湿式报警阀启动后，带延迟器的水力警铃在85s时发出报警铃声","湿式：末端装置处放水，当报警阀进水压力大于0.14mpa、放水流量大于1l\u002Fs时，报警阀应及时启动，带延的水力警铃在5~90s内发出报警铃声，不带的应在15s内发出报警铃声，压力开关应及时动作，启动消防泵，并反馈信号。 干式：开启试验阀。 雨淋：宜采用检测、试验管道进行，自、手启动的应在15s内启动；大于200mm的在60s内启动。当报警水压大于0.05mpa时，水力警铃应发出报警铃声。P152-164",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]