[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-934978":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},934978,605,1,"单选题","(2018年真题) 某消防技术服务机构对某单位安装的自动喷水灭火系统进行检测，检测结果如下:(1)开启末端试水装置，以1.1L\u002Fs的流量放水，带延迟功能的水流指示器15s时动作:(2)末端试水装置安装高度为1.5m(3)最不利点末端放水试验时，自放水开始至水泵启动时间为3min(4)报警阀距地面的高度为1.2。 上述检测结果中，符合现行国家标准要求的共有()",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","1个",false,{"key":16,"text":17,"correct":14},"B","2个",{"key":19,"text":20,"correct":21},"C","4个",true,{"key":23,"text":24,"correct":14},"D","3个","湿式报警阀组调试时，从试水装置处放水，当湿式报警阀进水压力大于0.14MPa、放水流量大于1L\u002Fs时，报警阀启动，带延迟器的水力警铃在5~90s内发出报警铃声，不带延迟器的水力警铃应在15s内发出报警铃声，压力开关动作，并反馈信号。末端试水装置和试水阀应有标识，距地面的高度宜为1.5m，并应采取不被他用的措施。湿式自动喷水灭火系统的最不利点做末端放水试验时，自放水开始至水泵启动时间不应超过5min。报警阀阀体底边距室内地面高度为1.2m，侧边与墙的距离不小于0.5m；正面与墙的距离不小于1.2m；报警阀组凸出部位之间的距离不小于0.5m。P152-164",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]